Details
Air-cooled chiller CLASSIC Cool TT-5500
The TT-5'500 is the entry point into the Tool-Temp CLASSIC Cool chiller line — a compact, air-cooled unit for small production cells and single-machine cooling loads, with optional heating to double as a light temperature control unit. It is available in three refrigerant variants matched to the ambient conditions on the shop floor: the standard R-134a version, the high-performance R-407c (HP) version for higher cooling output at moderate ambient temperature, and the low-GWP R-1234yf (LG) eco version.
Available variants (air-cooled)
| Variant | Refrigerant | Cooling capacity | Ambient temp. range | Max. ambient | Fill volume | Pump | Motor |
|---|---|---|---|---|---|---|---|
| TT-5'500 | R-134a | 5 kW | +10°C to +40°C | +45°C | 25 L | Type E, 4.5 bar / 75 l/min | 0.75 kW |
| TT-5'500 LG | R-1234yf | 4.5 kW | +10°C to +40°C | +45°C | 25 L | Type E, 4.5 bar / 75 l/min | 0.75 kW |
| TT-5'500 HP | R-407c | 6 kW | +10°C to +30°C | +30°C | 25 L | Type E, 4.5 bar / 75 l/min | 0.75 kW |
Technical data
- Dimensions (L×W×H): 950×365×740 mm, incl. castors
- Weight: approx. 115 kg empty
- Noise level: 66 dBA at 3 m distance
- Hermetically sealed compressor
- Air volume: 1'700 m³/h
- Connections: ¾" BSPP female thread (to/from mould), ½" BSPP female thread (auto. water refill)
- Colour: Silvergrey RAL 7001, optional stainless-steel housing
Controller and functions (MP-888)
- Self-optimizing temperature controller with temperature display in 1/10°C steps
- Display in °C or °F and l/min or gal/min
- Automatic or manual refill
- Optional integrated heating for combined cooling/heating operation
- Leakstopper device — pressure and vacuum mode possible (device-dependent)
- Analogue interfaces: 0–10 V, (0)4–20 mA input, 0–10 V output
Safety
- Automatic level control with prewarning at low water level
- Electronic temperature limitation and monitoring in the controller
- Mechanical safety thermostats and mechanical pressure monitoring in the refrigeration circuit
- Visual and acoustic fault indications
- Integrated circuit breakers, main switch, transformer and motor protection switch
- Moisture indicator for the refrigeration circuit, protection class IP44, CE labelling
Perotec Systems is the Tool-Temp partner for Serbia, Croatia, Bosnia and Herzegovina, North Macedonia and Montenegro — contact us to size the right CLASSIC Cool TT-5'500 variant for your machine and ambient conditions.