Air-cooled chiller CLASSIC Cool TT-5500

The TT-5'500 is the entry point into the Tool-Temp CLASSIC Cool chiller line — a compact, air-cooled unit for small production cells and single-machine cooling loads, with optional heating to double as a light temperature control unit. It is available in three refrigerant variants matched to the ambient conditions on the shop floor: the standard R-134a version, the high-performance R-407c (HP) version for higher cooling output at moderate ambient temperature, and the low-GWP R-1234yf (LG) eco version.

Available variants (air-cooled)

Variant Refrigerant Cooling capacity Ambient temp. range Max. ambient Fill volume Pump Motor
TT-5'500 R-134a 5 kW +10°C to +40°C +45°C 25 L Type E, 4.5 bar / 75 l/min 0.75 kW
TT-5'500 LG R-1234yf 4.5 kW +10°C to +40°C +45°C 25 L Type E, 4.5 bar / 75 l/min 0.75 kW
TT-5'500 HP R-407c 6 kW +10°C to +30°C +30°C 25 L Type E, 4.5 bar / 75 l/min 0.75 kW

Technical data

  • Dimensions (L×W×H): 950×365×740 mm, incl. castors
  • Weight: approx. 115 kg empty
  • Noise level: 66 dBA at 3 m distance
  • Hermetically sealed compressor
  • Air volume: 1'700 m³/h
  • Connections: ¾" BSPP female thread (to/from mould), ½" BSPP female thread (auto. water refill)
  • Colour: Silvergrey RAL 7001, optional stainless-steel housing

Controller and functions (MP-888)

  • Self-optimizing temperature controller with temperature display in 1/10°C steps
  • Display in °C or °F and l/min or gal/min
  • Automatic or manual refill
  • Optional integrated heating for combined cooling/heating operation
  • Leakstopper device — pressure and vacuum mode possible (device-dependent)
  • Analogue interfaces: 0–10 V, (0)4–20 mA input, 0–10 V output

Safety

  • Automatic level control with prewarning at low water level
  • Electronic temperature limitation and monitoring in the controller
  • Mechanical safety thermostats and mechanical pressure monitoring in the refrigeration circuit
  • Visual and acoustic fault indications
  • Integrated circuit breakers, main switch, transformer and motor protection switch
  • Moisture indicator for the refrigeration circuit, protection class IP44, CE labelling